(* =============================================================================== Project : PLC_Library Device : - Path : Fastwel Name : AIM725_Status Type : FUNCTION_BLOCK Exported : 2026-07-31 11:16:16 =============================================================================== *) FUNCTION_BLOCK AIM725_Status (* Модуль формирования статуса Гистерезис по отключению и задержка по включению -1 - нет связи с датчиком 0 - не определено 1 - норма 2 - предупредительный по нижнему уровню 3 - аварийный по нижнему уровню 4 - предупредительный по верхнему уровню, 5 - аварийный по верхнему уровню *) VAR_INPUT Input: REAL; fail_hi: REAL:=3.402823466E+38; delta_fail_hi: REAL := 0; time_fail_hi: TIME :=t#0s; warn_hi: REAL:=3.402823466E+38; delta_warn_hi: REAL := 0; time_warn_hi: TIME :=t#0s; warn_low: REAL:=-3.402823466E+38; delta_warn_low: REAL := 0; time_warn_low: TIME :=t#0s; fail_low: REAL:=-3.402823466E+38; delta_fail_low: REAL := 0; time_fail_low: TIME :=t#0s; Modul_status: BYTE; Chanel_num: BYTE; END_VAR VAR_OUTPUT Status: INT; T_mod: INT; END_VAR VAR (* !!! ВНУТРЕННИЕ НЕВЫХОДНЫЕ ПЕРЕМЕННЫЕ!!! *) TON_fail_hi: TON; TON_warn_hi: TON; TON_warn_low: TON; TON_fail_low: TON; (* !!! ВНУТРЕННИЕ ВЫХОДНЫЕ ПЕРЕМЕННЫЕ!!! *) fail_hi_st: BOOL; warn_hi_st: BOOL; normal_st: BOOL; warn_low_st: BOOL; fail_low_st: BOOL; no_signal_st: BOOL; END_VAR (*----- IMPLEMENTATION -----*) no_signal_st := (Input <= - REAL#200 OR ((Modul_status.0 OR Modul_status.4 OR Modul_status.5) AND Chanel_num = 1) OR ((Modul_status.1 OR Modul_status.6 OR Modul_status.7) AND Chanel_num = 2) OR Modul_status.2 OR Modul_status.3); IF no_signal_st THEN T_mod := - INT#500; ELSE T_mod := REAL_TO_INT(Input); END_IF; TON_fail_low(IN := ((Input <= fail_low) AND NOT(no_signal_st)), PT := time_fail_low); IF TON_fail_low.Q THEN fail_low_st := TRUE; ELSIF (Input > fail_low + delta_fail_low) THEN fail_low_st := FALSE; END_IF; TON_warn_low(IN := ((Input <= warn_low) AND NOT(no_signal_st) AND NOT(TON_fail_low.Q)), PT := time_warn_low); IF TON_warn_low.Q THEN warn_low_st := TRUE; ELSIF (Input > warn_low + delta_warn_low) THEN warn_low_st := FALSE; END_IF; TON_fail_hi(IN := ((Input >= fail_hi) AND NOT(no_signal_st)), PT := time_fail_hi); IF TON_fail_hi.Q THEN fail_hi_st := TRUE; ELSIF (Input < fail_hi - delta_fail_hi) THEN fail_hi_st := FALSE; END_IF; TON_warn_hi(IN := ((Input >= warn_hi) AND NOT(no_signal_st) AND NOT(TON_fail_hi.Q)), PT := time_warn_hi); IF TON_warn_hi.Q THEN warn_hi_st := TRUE; ELSIF (Input < warn_hi - delta_warn_hi) THEN warn_hi_st := FALSE; END_IF; normal_st := (NOT(no_signal_st) AND NOT(fail_low_st) AND NOT(warn_low_st) AND NOT(warn_hi_st) AND NOT(fail_hi_st)); IF no_signal_st THEN Status := - INT#1; ELSIF fail_hi_st THEN Status := INT#5; ELSIF fail_low_st THEN Status := INT#3; ELSIF warn_hi_st THEN Status := INT#4; ELSIF warn_low_st THEN Status := INT#2; ELSIF normal_st THEN Status := INT#1; ELSE Status := INT#0; END_IF; END_FUNCTION_BLOCK