FUNCTION_BLOCK CONFIRMATION
(*
Квитирование
*)
VAR_INPUT
Alarm: BOOL; // Авария
ControlState_On: BOOL; // Управление с текущего поста
Sound_Off: BOOL; // Сигнал снятия звука
Confirmation: BOOL; // Сигнал квитирования
END_VAR
VAR_OUTPUT
Lamp_Alarm_C: WORD; // Лампа аварии
Lamp_Confirmation_C: WORD; // Лампа квитирования
Buzzer_C: WORD; // Управление звонком
END_VAR
VAR
Alarm_Not_Sound_Off: BOOL;
Alarm_Not_Confirm: BOOL;
R_TR1: R_TRIG;
R_TR2: R_TRIG;
R_TR3: R_TRIG;
END_VAR
(*----- IMPLEMENTATION -----*)
R_TR1(CLK:=Confirmation); IF R_TR1.Q THEN Alarm_Not_Confirm:=0; END_IF;
R_TR2(CLK:=Sound_Off); IF R_TR2.Q THEN Alarm_Not_Sound_Off:=0; END_IF;
R_TR3(CLK:=Alarm); IF R_TR3.Q AND ControlState_On THEN Alarm_Not_Confirm:=1; Alarm_Not_Sound_Off:=1; END_IF;
IF NOT ControlState_On THEN Alarm_Not_Confirm:=0; Alarm_Not_Sound_Off:=0; END_IF;
IF NOT Alarm AND NOT Alarm_Not_Confirm THEN Lamp_Alarm_C:=0; Lamp_Confirmation_C:=0; END_IF;
IF Alarm AND NOT Alarm_Not_Confirm THEN Lamp_Alarm_C:=1; Lamp_Confirmation_C:=0; END_IF;
IF Alarm_Not_Confirm THEN Lamp_Alarm_C:=2; Lamp_Confirmation_C:=1; END_IF;
IF Alarm_Not_Sound_Off THEN Buzzer_C:=2; ELSE Buzzer_C:=0; END_IF;
END_FUNCTION_BLOCK